Skip to main content
Tank & Line Compliance Testing

Line leak detector certification.

Annual mechanical and electronic line leak detector certification per the PEI RP1200 C-9 procedure, under EPA 40 CFR 280.40. Estabrook-tester verified.

Manufacturer-certified · EPA 40 CFR Part 280 · Testing tanks since 1997

What we test

Mechanical line leak detectors (MLLD) and electronic line leak detectors (ELLD/PLLD). Annual certification is required by EPA on every pressurized fuel line.

Method

How we run it.

PTTI follows the PEI RP1200 Appendix C-9 procedure, a 17-step process using a calibrated test apparatus that simulates a 3 GPH leak at 10 PSI.

The calibrated apparatus is connected to the line and introduces a simulated leak at the metered rate while the line is held at metering pressure. The detector is then evaluated against the PEI RP1200 C-9 pass criteria.

A mechanical leak detector passes if the line holds at metering pressure for the full duration of the simulated leak. An electronic detector passes if it generates an alarm and, where applicable, shuts down the submersible turbine pump.

Equipment, schedule, and record
Equipment
Estabrook Leak Detector Tester and its calibrated test apparatus.
Frequency
Annual certification on every pressurized fuel line.
Deliverable
An audit-ready leak detector certification record, sent after the visit and built to the PEI RP1200 C-9 standard your inspector checks against. PTTI prepares the record; your operator files it with the state.
Common failure modes

What we look for.

  1. 1

    Check valve clogging

    The functional element fails to seat properly, allowing flow during the simulated leak.

  2. 2

    Sensitivity drift

    The detector triggers at a different leak rate than spec.

  3. 3

    Corrosion or mechanical wear

    Internal components reach the end of their service life and require replacement.

Get a quote

Leak detector certification due? Tell us about your site.

Annual mechanical and electronic line leak detector certification under EPA 40 CFR 280.40, bundled with your line tightness visit. Tell us about your site and we'll have a quote back to you fast.

Questions

Frequently asked.

How often does a line leak detector need to be certified?

Annually, under EPA 40 CFR 280.40, on every pressurized fuel line. PTTI typically certifies the leak detectors on the same visit as the annual line tightness test.

What is the difference between mechanical and electronic leak detectors?

A mechanical line leak detector passes if the line holds at metering pressure for the full duration of a simulated 3 GPH leak. An electronic detector passes if it generates an alarm and, where applicable, shuts down the submersible turbine pump. PTTI tests both to the PEI RP1200 C-9 procedure.

What happens if my leak detector fails certification?

PTTI documents the result and identifies the cause, commonly a clogged check valve, sensitivity drift, or worn internals. PTTI prepares the records, and the operator handles any state filing.

Call (801) 886-9224 Get a quote